The proceed as follows :
- Stop the compressor,for at least two hours.
- Close the compressor suction stop valve and any valves between the condenser and receiver.
- Loosen the pressure gauge in order to check it.
- Start the cooling pump.After a short time,measure the temperature of the cooling water,which should then be compared with the reading onthe pressure gauge.If the pressure gauge shows a higher pressure than that which corresponds to the cooling water temperature,non condensable gases are present in the condenser.
- The gases should be purged from the top of the condenser by carefully opening the purging valve or perhaps loosening a screwed connection or something similiar.
- Repeat the purging process a few more times,at intervals of 3-4 minutes during which the cooling water should run continuously as any water valves which may be installed can otherwise become blocked in open position.
- If purging is constantly required,please check the plant for leaks.